NEPTUNE
GLYCOL FEED SYSTEM
Models G-50-1, G-50-1A, G-50-2A, G-100-1A, G-100-2A
Lansdale, PA 19446 Tel: 215-699-8700 Fax: 215-699-0370
REV NO 6 – 01/08/04
ZL106838
OPERATING &
INSTRUCTION
MANUAL
Przeglądanie stron 0
1 2 3 4 5 6 ... 14 15

Podsumowanie treści

Strona 1 - INSTRUCTION

NEPTUNE GLYCOL FEED SYSTEM Models G-50-1, G-50-1A, G-50-2A, G-100-1A, G-100-2A Lansdale, PA 19446 Tel: 215-699-8700

Strona 2 - GENERAL DESCRIPTION

BRONZE ROTARY GEAR PUMP INSTRUCTIONS continued ……. Flow By-Pass When a flow by-pass system is used to control output from the pump, the bypassed fl

Strona 3 - OPERATION

Mechanical Seals Pumps equipped with mechanical seals are of the standard pusher bellows type or wedge style. They can be expected to provide long a

Strona 4

PRESSURE SWITCH INSTRUCTIONS SQUARE D Commercial Pressure Switch Class 9013, Model FSG29J99 Model FSG29J99 CUT-OUT RANGE 20-60 PSI ADJUSTAB

Strona 5

PRESSURE SWITCH INSTRUCTIONS continued ….. SET POINT ADJUSTMENTS The pressure switch is set at the factory to the operating point(s) marked on the ou

Strona 6

INSTALLATION INSTRUCTIONS LL-3 (L-30N) LIQUID LEVEL SWITCH MODEL L30N LIQUID LEVEL SWITCH INSTALLATION AND OPERATING INSTRUCTIONS Installation: The

Strona 7

MODEL L30N LIQUID LEVEL SWITCH INSTALLATION AND OPERATING INSTRUCTIONS 5). Apply slip on terminals to appropriate contacts of micro switch. Slide c

Strona 8 - Bronze Rotary Gear Pumps

I. GENERAL DESCRIPTION Neptune Chemical Pump Company’s Glycol Feed System is intended for the automated addition of glycol into closed loop chille

Strona 9

II. OPERATION The glycol feeder is provided with a control panel with HAND/OFF/AUTO selector switch. When the panel is switched to the AUTO posi

Strona 10

TROUBLESHOOTING PROBLEM PROBABLE CAUSE Pump is running but is 1. The motor rotation is incorrect. The not pumping anything proper rota

Strona 14 - LIQUID LEVEL SWITCH

Bronze Rotary Gear Pumps Installation, Operation, and Maintenance Instruction INTRODUCTION Congratulations for choosing an Oberdorfer pump,the Indus

Strona 15

BRONZE ROTARY GEAR PUMP INSTRUCTIONS continued ……. INSTALLATION Site Preparation Choose a site that allows easy access to the pump for maintenance